Airflow testing and commissioning
Calibrated flow-hood testing and commissioning sheets for fans, MEV and MVHR.
Guide
Part F rates
Approved Document F (2021 edition) sets minimum extract rates for homes in England: 15 litres a second for a bathroom, 30 for a kitchen with a cooker hood or 60 without, 30 for a utility room and 6 for a WC, with whole-home rates based on the number of bedrooms.
Kitchen 30 l/s with a cooker hood or 60 l/s elsewhere; utility 30 l/s; bathroom 15 l/s; WC 6 l/s.
For continuous systems the whole-dwelling rate rises with bedrooms: 19 l/s for one bedroom, 25 for two, 31 for three, 37 for four and 43 for five, and supply should be at least 0.3 l/s per square metre of floor where that is higher.
Yes. Mechanical ventilation in new dwellings must be tested with a calibrated flow device and the results recorded on a commissioning sheet for building control.
Natural or extract-only ventilation relies on background ventilators in habitable rooms; whole-home MVHR should not have them.
No. Each nation has its own guidance, so rates and paperwork can differ. We design to the rules where the job is.
Try our ventilation rate calculator to work out the whole-dwelling rate and extract rates for an English home.